This single-phase DIN rail kWh meter is a new generation of single-phase electronic watt-hour meters, adopting micro-electronic techniques, LSI circuits and advanced digital and SMT techniques. The meter is in conformity with the relevant technical requirements of Class 1, Class 2 and IEC62052-11, IEC62053-21. It accurately and directly measures 50/60 Hz active energy consumption from single-phase AC electricity grids. The Current specification is an important parameter for energy meters as it signifies a meter's ability to accurately measure the power consumed by a user's electrical load. There are generally two parts to this specification: the basic Current (Ib) for direct-connected meters and the maximum Current I max. Of these Current ratings, you will typically see the Current specification defined in terms of Ib with the I max value shown in parentheses. For example, some common values for the energy meter Current specification include 5 (40) A, 5 (80) A or 10 (100) A.
LCD Display (with blue backlight)
pulsed output
LED indicator
voltage: 230 V
Current: 5 (80) A
accuracy class: 1.0
frequency: 50 / 60 Hz
Display mode: LCD 5+1 digits = 99999.9 kWh
power consumption: <= 0.4 W (8 VA)
temperature range: -20 to 65 °C
LED indicator: 1 blink per pulse
with PNP transistor
RESET: To reset the Device, keep your finger on the infrared eye (marked Reset) for 3 to 12 seconds. Upper row will reset to ZERO Lower row shows the total of kW/h permanently.
pulsed output: 1000 imp/kWh
voltage: 12 to 27 V
Current: 27 mA
impulse width: 90 ms
notes:
A qualified technician should install and service this Device.
The measurements provided by this Device are for information purposes only.
dimensions (LxWxH): 100 x 35 x 60 mm
cable cross-sectional area: min. 7 mm², max: 38 mm²
torque: max. 140 Nm
width: 2 DIN modules