Three-phase four-wire electronic DIN rail kWh meter with pulse counting output. Very accurate, reliable, light, and compact Device.
LCD Display (with blue backlight)
pulsed output
LED indicator
The Current specification is an important parameter for energy meters as it signifies a meter's ability to accurately measure the power consumed by a user's electrical load. There are generally two parts to this specification: the basic Current (Ib) for direct-connected meters and the maximum Current I max. Of these Current ratings, you will typically see the Current specification defined in terms of Ib with the I max value shown in parentheses. For example, some common values for the energy meter Current specification include 5 (40) A, 5 (80) A or 10 (100) A.
voltage: 3 x 230 / 400 V
Current: 10 (100) A
accuracy class: 1.0
frequency: 50 / 60 Hz
Display mode: LCD 6+1 digits = 999999.9 kWh
power consumption: <=2 W (10 VA)
temperature range: -20 to 55 °C
LED indicator: 1 blink per pulse
pulsed output: 800 imp/kWh
voltage: 12 to 27 V
Current: 27 mA
impulse width: 90 ms
dimensions: 122.5 x 115 x 65 mm
weight: 415 g
notes:
A qualified technician should install and service this Device.
The measurements provided by this Device are for information purposes only.
not resettable
with PNP transistor
cable cross-sectional area: min: 7mm², max: 50 mm²
torque: max. 140 Nm
width: 7 DIN modules