High-performance online security
SLC TWIN RT3, in its range from 1,000 VA to 3,000 VA, represents the perfect balance in all aspects: its efficient operation as a double conversion UPS, the optimized battery charging system, the power density, the high degree of connectivity (with the consequent immediacy of the information), the flexibility offered by the variety of functions of the output sockets (identified by colour), the automatic detection system of external battery modules, the beauty of its design of floating prisms with finished top quality,..., no aspect has been left aside considering the criticality of the systems to be protected.
As usual in SLC TWIN RT equipment, they are presented in a 2U rack format, easily convertible to tower, with display and adjustable keypad, according to installation needs.
The extended autonomy requirements of the system are satisfactorily achieved thanks to the additional battery modules and the equipment with an improved 8A charger. The charger stands out for having a "rest" mode during which it does not send current to the batteries, thus reducing stress and extending its useful life.
Applications:
Protection for small format priority systems
Salicru's SLC TWIN RT3 series offers a high level of security against all types of electrical disturbances and interruptions; guaranteeing continuity in IT servers, voice and data networks, CAD/ CAM, document management, unified communications (UC) or video streaming.
Features:
SLC TWIN RT3 has, as standard in all its range, a native ethernet port and a Wi-Fi device, as an option. Either wirelessly or via cable, we can integrate the UPSs into the IoT environment and manage them through the cloud, our NIMBUS APP, and the web portal; providing numerous advantages, both from the point of view of operation (optimization, prevention, analysis, maintenance), and reliability (early detection of failures, remote alarm management, operation record, ...).
SLC TWIN RT3 maintains autonomy extension options through additional battery modules in 2U rack format, always preserving the design language of the series and dimensional harmony. The modules are interconnected with each other and with the UPS by means of a solid Anderson aerial connector and an RJ45 cable, for their intelligent management.
The load currents and the bus voltage are selectable by the user, adapting to the maximum autonomy option that be available. For installations that require more current input in the battery charging cycle, there is the B1 range equipped with a high-capacity charger, maintaining the 2U format.
Technology: On-line double conversion
Format: Convertible tower/rack with rotating display
Input:
Nominal voltage: 200 / 208 / 220 / 230 / 240 V
Voltage range: 110~300V( note 1)
Rated frequency: 50/60Hz (auto detection)
Frequency range: 50±5%/60±5%
Total Harmonic Distortion (THDi): <5 %
Output:
Power factor: 1
Rated voltage: 200 / 208 / 220 / 230 / 240 V(note 2)
Voltage accuracy: ±1%
Total Harmonic Distortion (THDv): <1% linear load / <5% non-linear load
Sync Frequency: 50 ±5 Hz/60 ±6 Hz
On-line performance: ≥89 ÷ 93 %
Eco-mode efficiency: ≥96 ÷ 97 %
Admissible overloads Battery mode: 105 ÷ 125% for 2 min/125 ÷150% for 10 s/>150% for 500 ms
Admissible overloads Bypass mode: 105 ÷ 125% for 10 min/125 ÷150% for 5 min/>150% for 500 ms
Admissible overloads Online mode: 105 ÷ 125% for 5 min/125 ÷150% for 30 s/>150% for 500 ms
Programmable taps: Yes, for critical/non-critical loads (4/4) (note 3)
Battery:
Battery Type: Sealed Pb-Ca, AGM, Maintenance Free
Charge Type: 3-State Smart Charge
Recharge Time: 3 hours to 90%
Maximum number of EBM: 4
Charger:
Voltage compensation for temperature: Yes
Charging current: 1.5 A (8 A for B1 units)
Communication:
Ports: USB-HID/RS-232 /RJ-45/HDMI for wifi dongle
Smart slot: For SNMP/AS400/MODBUS
Monitoring Software: Software for Windows, Linux and Mac/APP for iOS and Android/WEB Portal
Dimensions: 445 mm (depth) x 438 mm (width) x 86 mm (height)
Weight: 15,6 Kg
Notes:
(1) 110 ÷ 160 V with linear load reduction at 50%
(2) Power reduction to 80% for 200, and 90% for 208 V
(3) For the 3 kVA model, there is an additional fifth non-programmable IEC C19 output.